Product specification
TRANSFORMER CORE
- Three phase, forced air cooled, class H, 50kVA
- Primary winding connected in Delta
- Secondary winding connected in Star
- Auxiliary winding: 110V a.c. 3.3kVA single phase
PRIMARY SUPPLY
- Primary voltage: 380V, 415V, 440V
- Primary current: 76A, 70A, 66A
- Frequency: 50/60 Hz
PROTECTION
- Three phase 80A circuit breaker with shunt trip
- Three primary core winding over temperature thermostats linked to circuit breaker shunt trip
SECONDARY OUTPUTS
- Output: 32.5V for 30V heating element operation
- Auxiliary outputs: Two 110V, 10A, 50/60Hz output sockets
- Number of temperature controlled output channels: 36 channels
- Maximum load per output channel: 1.35kW
- Maximum current per output channel: 45A
CONSTRUCTION
- Case: 304 Stainless Steel case fitted with four 150mm nylon wheels
DIMENSIONS
- Weight: 362kg
- Height: 1420mm
- Width: 680mm
- Depth: 665mm
SWITCHING
- 36 single pole, 80A, contractors with 110V a.c. coil
TEMPERATURE CONTROL
- Temperature measurement, display and control: Fahrenheit or Centigrade
- Temperature ramp up and down in degrees per hour
- Hold/soak temperature set point and hold/soak time period setting
|